Inspection Detail
Inspection: 307568188 - Potomac Electric Power Company
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Potomac Electric Power Company
3823 64th Avenue
Landover Hills, MD 20784
Mailing Address:
1900 Pennsylvania Avenue, Nw Room 515, Washington, DC 20068
Union Status: Union
SIC:4911
NAICS: 221122/Electric Power Distribution
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/18/2005
Emphasis: S:Falls, S:Amputations Const. & Man., S:Electrocution
Case Closed: 01/25/2005
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102356680 |
Investigation Summary
A power line worker was troubleshooting an outage on an overhead power line. He climbed a utility pole to repair cutouts on a 13-kilovolt, three-phase circuit supplying an apartment complex. One of the cutouts had opened, and the employee had manually opened the other two cutouts. As he was repairing the cutouts, he contacted the over-arm tap, which was still energized, and was electrocuted. The employee had been using a body belt and positioning strap and had been wearing a hardhat and pole climbers. However, he had not been using rubber insulating gloves or sleeves.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CUTOUT SWITCH, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 307568188 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate