Inspection Detail
Inspection: 304529936 - Princess Bayside Beach Hotel
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Princess Bayside Beach Hotel
4801 Coastal Highway
Ocean City, MD 21842
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:7011
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/26/2001
Emphasis:
Case Closed: 10/31/2001
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100968601 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 5 | 1 | 6 | |||
| Current Violations | 5 | 1 | 6 | |||
| Initial Penalty | $7,875 | $0 | $0 | $0 | $0 | $7,875 |
| Current Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100303 G02 I | 09/12/2001 | 09/17/2001 | $400 | $875 | $0 | I - Informal Settlement | ||
| 2. | 02001 | Serious | 19100332 B01 | 09/12/2001 | 10/15/2001 | $600 | $1,750 | $0 | I - Informal Settlement | ||
| 3. | 02002 | Serious | 19100333 A | 08/21/2001 | 09/23/2001 | $600 | $1,750 | $0 | I - Informal Settlement | ||
| 4. | 02003 | Serious | 19100333 A01 | 09/12/2001 | 09/15/2001 | $600 | $1,750 | $0 | I - Informal Settlement | ||
| 5. | 03001A | Serious | 19101200 E01 | 09/12/2001 | 10/15/2001 | $300 | $1,750 | $0 | I - Informal Settlement | ||
| 6. | 03001B | Serious | 19101200 F05 I | 09/12/2001 | 09/17/2001 | $0 | $0 | $0 | - | ||
| 7. | 03001C | Serious | 19101200 H01 | 09/12/2001 | 10/15/2001 | $0 | $0 | $0 | I - Informal Settlement | ||
| 8. | 03001D | Serious | 50406 A01 | 09/12/2001 | 09/17/2001 | $0 | $0 | $0 | - | ||
| 9. | 04001 | Other | 19100303 G01 | 09/12/2001 | 09/17/2001 | $0 | $0 | $0 | - |
Investigation Summary
Employee #1 was working on the fifth floor, south side, of the Princess Bayside Beach Hotel. Someone from housekeeping, seeing an unplugged air conditioning unit, had plugged it into the receptacle, and the receptacle arced. The receptacle was protected by a circuit breaker located on the ground floor. Employee #1 wanted to check for electric current at the wall-mounted switch on the east wall of the hallway, which controlled power to the receptacle that had arced. He removed the faceplate from the switch and used a coworker's personal Fluke meter to check both sides of the switch for current to the receptacle. The test Employee #1 conducted did not indicate that any current was going to the receptacle. Employee #1 removed the faceplate of the receptacle and the receptacle itself. He then removed the ungrounded circuit conductor from the receptacle and received an electric shock through his hand.
Keywords: MAINTENANCE, E GI III, RECEPTACLE, ELECTRICAL, LOCKOUT, ELECTRIC SHOCK, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 304529936 | Non Hospitalized injury | Electric Shock | Occupation not reported |
Translate