Inspection Detail
Inspection: 300326964 - Mount Vernon Mills, Inc.
Inspection Information - Office: Mobile Area Office
Site Address:
Mount Vernon Mills, Inc.
1 Lower River Rd.
Tallassee, AL 36078
Mailing Address:
P.O. Box 667, Tallassee, AL 36078
Union Status: NonUnion
SIC:2211
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 12/03/1996
Emphasis:
Case Closed: 04/14/1997
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100450105 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $18,000 | $0 | $0 | $0 | $0 | $18,000 |
| Current Penalty | $18,000 | $0 | $0 | $0 | $0 | $18,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 03/24/1997 | 03/28/1997 | $4,500 | $4,500 | $0 | - | ||
| 2. | 01002 | Serious | 19100333 B02 IIA | 03/24/1997 | 03/29/1997 | $4,500 | $4,500 | $0 | - | ||
| 3. | 01003 | Serious | 19100333 B02 IIB | 03/24/1997 | 03/29/1997 | $4,500 | $4,500 | $0 | - | ||
| 4. | 01004 | Serious | 19100333 B02 IVB | 03/24/1997 | 03/29/1997 | $4,500 | $4,500 | $0 | - |
Investigation Summary
An electrical crew was working in a substation. There were two substations side by side--one was for the main power for the mill it supplied, and the other, in which the crew was working, was for the plant's air conditioning system. The crew was changing the capacitor for the substation under the supervision of the plant engineer, who had made the decision to use plant employees rather than a contractor to do the work. The engineer wrote down the procedure to be followed, including the energy sources that would be isolated and the sequence in which to isolate them. However, the engineer had not identified an uninsulated 13.8-kilovolt conductor that came from the main substation and passed through the second substation. As part of this job, an electrician, who had no experience working in a substation, started to remove a fuseholder for the capacitor. The fuseholder was screwed to a metal bar that was welded to the substation steel structure. When the employee began to unscrew the fuseholder, the weld on the metal bar broke, causing the employee to lose his balance and fall backward. He contacted the energized conductor and a lightning arrestor that was behind him. He was electrocuted.
Keywords: LIGHTNING ARRESTER, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, FALL, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 300326964 | Fatality | Electric Shock | Electricians |