Inspection Detail
Inspection: 1689185.015 - Timothy Guinn
Inspection Information - Office: Dallas Area Office
Site Address:
Timothy Guinn
9236 Church Rd.
Dallas, TX 75231
Mailing Address:
4217 Cr 616, Alvarado, TX 76009
Union Status: NonUnion
SIC:
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Inspection Type: Referral
Scope: No Insp/Other
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/07/2023
Emphasis:
Case Closed: 09/01/2023
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 2064290 | ||
| Referral | 2140542 | Yes |
Investigation Summary
At 10:50 a.m. on August 4, 2023, an employee was installing the outer unit of an air conditioning system and he had installed the piping which passed a pressure test. The employee then went to vacuum the system to ensure all moisture was removed from it prior to charging. To power the vacuum pump, the employee had a homemade extension cord with a metal receptacle box attached to it. The employee used alligator clips to hook the receptacle box up to the wiring meant to power the unit. While hooking up the receptacle box the employee suffered an electrical shock. A coworker found the employee unresponsive and called emergency services. The emergency service operator directed the coworker to move the employee so CPR could be conducted until paramedics arrived. The coworker picked the employee up by wrapping his arms around his chest from behind to lay him on the concrete sidewalk next to the unit. When the coworker grabbed the employee, he felt electrical energy which stopped once the employee was moved. The employee was unable to be revived and died at the scene.
Keywords: CPR, Electric Cord, Electric Shock, Electrocuted, HVAC, Installing
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1689185.015 | 46 | M | Fatality | Laborers, except construction |
Translate