Inspection: 1454644.015 - U.S. Dept Of Army
Inspection Information - Office: Raleigh Area Office
Site Address:
U.S. Dept Of Army
Building #2449 Bragg Street - Fort Jackson
Columbia, SC 29207
Mailing Address:
3240 Sumter Avenue Fort Jacksion, Columbia, SC 29207
Union Status: Union
SIC:
NAICS: 928110/National Security
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership:
Safety/Health: Safety
Close Conference: 01/07/2020
Emphasis:
Case Closed: 04/13/2020
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 1531552 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100147 C04 I | 03/20/2020 | 03/27/2020 | $0 | $0 | $0 | Z - Issued | ||
| 2. | 01002 | Serious | 19100147 C07 I A | 03/20/2020 | 03/27/2020 | $0 | $0 | $0 | Z - Issued | ||
| 3. | 01003 | Serious | 19100147 D03 | 03/20/2020 | 03/27/2020 | $0 | $0 | $0 | Z - Issued |
Investigation Summary
At 1:30 p.m. on January 3, 2020, an employee was working as a civilian for a branch of the armed forces. He was a mechanical engineering technician. He and a coworker were working a boiler system. The employee was removing the cover to a pump on the system. The coworker had left to go to a truck. Because the water source had not been turned off, the pump was pressurized. The employee removed the bolts for the pump cover all at once and failed to allow the pressure to bleed out. When he removed the cover, the scalding water came out under pressure and splashed onto him. Steam filled the room, trapping the employee in a corner. He had to go back through the stream of scalding water to escape the room. He suffered first-, second-, and third-degree burns over his face, hands, head, legs, and torso. He was hospitalized at a burn center for several weeks.
Keywords: Boiler, Burn, Face, HVAC, Hand, Head, Hot Water, Leg, Lockout, Lockout/Tagout, Maintenance, Pressure, Pressure Release, Pump, Scald, Skin, Steam, Technician, Torso, Water
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1454644.015 | 37 | M | Hospitalized injury | Mechanical engineering technicians |
Translate