Inspection Detail
Inspection: 1449578.015 - Stout Electric
Inspection Information - Office: Nv-E-Las Vegas 0953220
Site Address:
Stout Electric
215 Codyerin Drive
Henderson, NV 89074
Mailing Address:
5160 West Patrick Suite #100, Las Vegas, NV 89118
Union Status: NonUnion
SIC:
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/30/2020
Emphasis:
Case Closed: 12/15/2020
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 1646340 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 1 | 5 | |||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $13,880 | $0 | $0 | $360 | $0 | $14,240 |
| Current Penalty | $6,940 | $0 | $0 | $360 | $0 | $7,300 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100333 A01 | 09/03/2020 | $3,470 | $3,470 | $0 | I - Informal Settlement | |||
| 2. | 01001B | Serious | 19100335 A01 I | 09/03/2020 | $0 | $3,470 | $0 | I - Informal Settlement | |||
| 3. | 01003A | Serious | 19100335 A02 I | 09/03/2020 | $3,470 | $3,470 | $0 | I - Informal Settlement | |||
| 4. | 01004B | Serious | 19100333 C02 | 09/03/2020 | $0 | $3,470 | $0 | I - Informal Settlement | |||
| 5. | 02001 | Other | NEVADA REVISED STATUTES 618.383(1 | 09/03/2020 | 09/16/2020 | $360 | $360 | $0 | I - Informal Settlement |
Investigation Summary
At 9:30 a.m. on December 2, 2019, an employee was attempting to slide a bolt from behind the bus bar, to use for the new breaker. The employee was called to a mobile home park to replace a main breaker inside an energized 240-volt electrical panel. The employee arrived at the work site and began his task. The employee attempted to install a bolt for the new breaker with an un-insulated plier, which made contact with live conductors, causing an arc blast. The employee incurred electrical burns on the right side of the body from the right hand up to the neck area and face. Other factors included: incorrect PPE was used, employee was inexperienced, and lack of supervision. The employee sustained first to second degree burns to the right side of the forearm, up to the neck area and second to third degree burns on the right hand, up to the mid-forearm. The employee was hospitalized.
Keywords: Arm, Bolt, Burn, Busbar, Circuit Breaker, Electric Arc Flash, Electrical Burn, Electrical panel, Energized, Face, Hand, Inexperience, Mobile Home, Neck, Protective Clothing, Supervision
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1449578.015 | 38 | M | Hospitalized injury | Electricians |