Standard Cited: 19100106 E05 IV Flammable liquids.
Inspection Nr: 934163.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 11/20/2013
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 12/13/2013
Gravity: 10
Report ID: 0830100
Contest Date:
Final Order: 12/09/2013
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/09/2013 | $7,000.00 | 12/13/2013 | Serious | |
| Penalty | Z: Issued | 11/20/2013 | $7,000.00 | 12/13/2013 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.106(e)(5)(iv): Where indicated by special hazards of operations, flammable or combustible liquid processing equipment were not protected by approved water spray systems, deluge systems, approved fire-resistant coatings, insulation, or any combination of these: a) Distillation Room; On or about August 19, 2013 and at times prior, employees were exposed to fire and explosion hazards while working in the distillation room containing flammable liquids such as but not limited to; Methyl alcohol, (Lacquer Thinners and Cleaning Solvents 105); Butyl Acetate, (Chroma Premier System 14385S and Chroma Premier Pro 74500S).