Violation Detail
Standard Cited: 19100147 C04 II C The control of hazardous energy (lockout/tagout).
Inspection Nr: 568720.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $0.00
Issuance Date: 01/31/2013
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 03/22/2013
Gravity: 10
Report ID: 0521100
Contest Date:
Final Order: 02/22/2013
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/22/2013 | $0.00 | 03/22/2013 | Serious | |
| Penalty | Z: Issued | 01/31/2013 | $7,000.00 | 03/20/2013 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.147(c)(4)(ii)(C): The energy control procedure did not clearly and specifically outline the steps for placement, removal and transfer of lockout devices or tagout devices and the responsibility for them: a) The employer's energy control procedures for group lockout did not address vesting primary responsibility or an authorized employee for a set number of employees working under them. b) The employer's energy control procedures for group lockout did not include the assignment of overall job-associated lockout responsibility to an authorized employee designated to coordinate affected workforce when more than one craft or department was involved. ABATEMENT CERTIFICATION AND ABATEMENT DOCUMENTATION REQUIRED.