Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1301570.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/25/2018
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 07/13/2018
Gravity: 5
Report ID: 0728900
Contest Date:
Final Order: 07/20/2018
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 06/25/2018 | $0.00 | 07/13/2018 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: The employer is failing to protect employees from electrical hazards associated with unsafe electrical work practices in hanging cords by the connectors without removing the tension and providing some form of strain relief. The most recent occurrence of this was found at the facility located at 1204 Jones St. Omaha, NE where the employer has employees operating equipment drawing power from temporary flexible cords strung along the ceiling connecting to a drop outlet without providing strain relief causing the exterior insulation to pull free from the connectors at both ends of the cord.