Violation Detail
Standard Cited: 19100269 O03 I Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1710688.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,839.00
Current Penalty: $4,839.00
Issuance Date: 04/08/2024
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 10
Report ID: 0729300
Contest Date:
Final Order: 04/22/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/22/2024 | $4,839.00 | Serious | ||
| Penalty | Z: Issued | 04/08/2024 | $4,839.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.269(o)(3)(i): The employer did not provide safeguarding within test areas to control access to test equipment or to apparatus under test that could become energized as part of the testing by either direct or inductive coupling and to prevent accidental employee contact with energized parts: On or about November 12, 2023, employees of Transformer Power Services LLC were commissioning and testing a 161Kv electrical transformer located at 15141 State Highway 177 in Jackson, Missouri. The employer did not provide safeguarding to employees when wiring a Caterpillar diesel generator into the control cabinet of the electrical transformer, under test. The 240v used to power the transformer control cabinet also provided a path to energize the auxiliary transformer. The arrestor cable and arrestors on top of the transformer became energized exposing employees to electrocution hazards.