Violation Detail
Standard Cited: 19100269 L08 V Electric Power Generation, Transmission, and Distribution.
This violation item has been deleted.
Inspection Nr: 1475244.015
Citation: 01003B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/03/2020
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 07/01/2020
Gravity: 1
Report ID: 0636900
Contest Date: 08/24/2020
Final Order: 09/23/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 09/23/2020 | $0.00 | 07/01/2020 | Serious | |
| Penalty | C: Contested | 08/24/2020 | $0.00 | 07/01/2020 | Serious | |
| Penalty | Z: Issued | 06/03/2020 | $0.00 | 07/01/2020 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2. At a site located at 1314 FM 1768, Olney, Texas; the employer did not ensure employees wear arc rated protective clothing when working on or near energize equipment rated at 690-volts or more. The employees were exposed to arc flash hazards.
Translate