Violation Detail
Standard Cited: 19100269 O03 I Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1466385.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,494.00
Current Penalty: $13,494.00
Issuance Date: 07/10/2020
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 07/16/2020
Gravity: 10
Report ID: 0111700
Contest Date:
Final Order: 08/06/2020
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/06/2020 | $13,494.00 | 07/16/2020 | Serious | |
| Penalty | Z: Issued | 07/10/2020 | $13,494.00 | 07/16/2020 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.269(o)(3)(i): The employer did not provide safeguarding within test areas to control access to test equipment or to apparatus under test that could become energized as part of the testing by either direct or inductive coupling and to prevent accidental employee contact with energized parts: Site - Employees performing testing on a Viper-S Solid Dielectric Automatic Circuit Recloser (serial #- 2019 0513 0737) were exposed to energized parts when the control power transformers were not disconnected as per the manufacturers instructions.