Violation Detail
Standard Cited: 19100269 L08 V Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1475096.015
Citation: 01002B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/05/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 05/20/2021
Gravity: 5
Report ID: 0830600
Contest Date: 11/03/2020
Final Order: 05/20/2021
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 05/20/2021 | $0.00 | 05/20/2021 | Other | |
| Penalty | C: Contested | 11/03/2020 | $0.00 | 10/30/2020 | Serious | |
| Penalty | Z: Issued | 10/05/2020 | $0.00 | 10/30/2020 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2: (a) On or about May 9, 2020, a FieldCore Service Solutions, LLC, employee was exposed to hazards from electric arcs while working with energized components at the base of wind turbine #46. The worker did not wear electrical-rated gloves where the estimated heat energy exceeded 2.0 Cal/cm2. The worker connecting to ground the breaker that was instead energized with 575 Volts and he sustained serious burns to his right hand. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Translate