Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1548205.015
Citation: 01001C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,502.00
Current Penalty: $0.00
Issuance Date: 01/25/2022
Nr Instances: 1
Nr Exposed: 380
Abatement Date: 05/16/2022
Gravity: 10
Report ID: 0521400
Contest Date:
Final Order: 02/15/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/15/2022 | $0.00 | 05/16/2022 | Serious | |
| Penalty | Z: Issued | 01/25/2022 | $14,502.00 | 03/03/2022 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. Clients' homes, hard-wired appliances: on or about August 16, 2021, installers and service technicians had their hands exposed to electric shock hazard likely to result in burns during voltage testing on or near energized electrical components operating above 50 volts because voltage-rated rubber insulating gloves with leather protectors were not provided. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d). Abatement Note: for compliance assistance, refer to OSHA 29 CFR 1910.137 "Electrical Protective Equipment" and NFPA 70E "Standard for Electrical Safety in the Workplace" (2018), www.nfpa.org.