Violation Detail
Standard Cited: 19100157 D02 Portable fire extinguishers.
Inspection Nr: 1439121.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/04/2019
Nr Instances: 1
Nr Exposed: 9
Abatement Date: 08/31/2020
Gravity: 5
Report ID: 0729300
Contest Date: 12/02/2019
Final Order: 04/20/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 04/20/2020 | $0.00 | 08/31/2020 | Serious | |
| Penalty | C: Contested | 12/04/2019 | $0.00 | 12/02/2019 | Serious | |
| Penalty | Z: Issued | 11/04/2019 | $0.00 | 12/02/2019 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.157(d)(2): Portable fire extinguishers for use on Class A fires were not distributed so that the travel distance for employees to any extinguisher was 75 feet or less: Such as in pot room C, instances existed where travel distance to an extinguisher was up to 200 ft. Abatement documentation is required for this violation.