Violation Detail
Standard Cited: 19260152 D02 Flammable liquids.
Inspection Nr: 1380079.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,978.00
Current Penalty: $1,989.00
Issuance Date: 04/17/2019
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 04/29/2019
Gravity: 10
Report ID: 0112600
Contest Date:
Final Order: 05/14/2019
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/14/2019 | $1,989.00 | 04/29/2019 | Serious | |
| Penalty | Z: Issued | 04/17/2019 | $3,978.00 | 04/29/2019 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.152(d)(2): A portable fire extinguisher having a rating of not less than 20-B units was not located between 25 feet and 75 feet from flammable liquid storage area(s) located outside: 241 Main Street, Sturbridge, MA: On or about February 22, 2019 the employer had not ensured that a fire extinguisher having a rating of not less than 20-B units was located not further an 75 feet from two 1000 gallon outside storage tanks which had previously contained diesel fuel.