Violation Detail
Standard Cited: 19100119 E03 I Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1363428.015
Citation: 01001
Citation Type: Serious
Abatement Status:
Initial Penalty: $13,260.00
Current Penalty: $0.00
Issuance Date: 05/02/2019
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 06/19/2019
Gravity: 10
Report ID: 0420600
Contest Date:
Final Order: 05/24/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/24/2019 | $0.00 | 06/19/2019 | Serious | |
| Penalty | Z: Issued | 05/02/2019 | $13,260.00 | 06/19/2019 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process: a. On or about November 17, 2018, at the extrusion area, the process hazard analysis conducted in March 2018 did not address the deactivation of de-ionizer fans from a power loss or partial power loss, exposing employees to a flash fire hazard. b. On or about November 17, 2018, at the extrusion area, the process hazard analysis conducted in March 2018 did not address the loss of re-grind material from a power loss or partial power loss, leading to the feed of virgin material to extruder #4 without a nucleating agent, exposing employees to a flash fire hazard.
Translate