Accident Summary Nr: 570606 - ELECTRIC SHOCK - GROUND FAULT IN MUSHROOM SHAKER MACHINE
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 2343564 | 02/06/1985 | 2033 | 0 | Heskett Foods Inc |
Abstract: AN EMPLOYEE WAS UNCLOGGING A DRAIN LOCATED UNDER A MUSHROOM SHAKER MACHINE. HE APPARENTLY LOST HIS BALANCE AND GRABBED THE ELECTRIC SUPPLY CABLE FOR THE MACHINE AS HE FELL. THERE WAS NO STRAIN RELIEF FOR THE CABLE'S CONDUCTORS AT THE MOTOR TERMINAL BOX. THE CABLE PULLED LOOSE, AND ONE CONDUCTOR IN THE CABLE SCRAPED THE BOX, WHICH CUT THROUGH THE INSULATION. THE GROUND FAULT ENERGIZED EITHER THE MACHINE OR THE CABLE; AND THE EMPLOYEE, WHO WAS STANDING IN WATER, WAS ELECTROCUTED.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 2343564 | Fatality | Electric Shock | Occupation not reported |