Accident Summary Nr: 201572203 - Three Employees Are Burned in Butane Explosion
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 304981053 | 09/27/2002 | 4213 | 0 | Basin Western Inc. |
Abstract: Employees #1 and #2 were in the wash bay of a trucking facility draining water from the bottom of a 1,400-gallon truck tank of butane BG mix into the floor drain. Employee #3 had stopped to talk with them. The water and butane mixture traveled via a drain pit from the back of the truck to the front of the truck. The vapors from the butane accumulated and reached the pilot light of a Hotsy, approximately 3.5 feet above the floor in a closet at the front of the wash bay. The pilot light ignited the butane vapors into a fireball. Flames engulfed the entire wash bay and shot 30 feet out the back door. Employees #1 and #2 sustained serious burns on their backs, arms, legs, and hands. Employee #3 suffered from burns primarily on his hands. All three workers were hospitalized for treatment of their injuries. Further investigation revealed that Employees #1 and #2 had misjudged the amount of butane mix coming off with the water.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 304981053 | Hospitalized injury | Burn/Scald(Heat) | Industrial truck and tractor equipment operators | ||
| 2 | 304981053 | Hospitalized injury | Burn/Scald(Heat) | Industrial truck and tractor equipment operators | ||
| 3 | 304981053 | Hospitalized injury | Burn/Scald(Heat) | Industrial truck and tractor equipment operators |