Accident Report Detail
Accident Summary Nr: 201043684 - Employee Is Struck and Killed by Fan Blades
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 311638324 | 02/07/2008 | 9199 | 921190 | City Of Henderson |
Abstract: On February 8, 2008, Employee #1 was working as an HVAC technician. He was working alone. The computer overseeing a cooling tower on the penthouse level roof of the city hall building had picked up a vibration alarm. It was displaying the alarm on a device being monitored by Employee #1. Employee #1 sent himself to determine the reason for the alarm. Employee #1 entered the cooling tower without shutting off or locking out power to the unit. The vibration switch consisted of a steel ball resting on a pedestal, just below which was a spring-loaded platform. If the ball landed on the platform due to excessive fan vibration, a circuit was opened. It is believed that Employee #1 stood on an A-frame ladder to reset the vibration switch. When he removed the steel ball from the platform, the circuit closed and the unit began running. Employee #1's jacket was caught up in the shaft of the unit's fan, located immediately above the vibration switch. As Employee #1 was suspended by one arm, his head was struck repeatedly by the blades of the rotating fan. Employee #1 subsequently died from his injuries. There were no witnesses to the incident.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 311638324 | Fatality | Cut/Laceration | Engineering technicians, n.e.c. |
Translate