Accident Report Detail
Accident Summary Nr: 200030963 - ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU GROUND WIRE
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 303119036 | 03/25/2000 | 1623 | 0 | The L.E. Myers Co. |
Abstract: A journeyman power line worker and a first-step apprentice were working from an uninsulated aerial lift, replacing bell insulators on a deenergized, three-phase, 345-kilovolt overhead power line. Steel towers supported the line. The crew had grounded the deenergized line, but had not set up an equipotential zone at the tower at which they were working. The power line worker was electrocuted when he contacted an end of an energized protective ground. The apprentice also received an electric shock when the aerial lift platform became energized. He was hospitalized for his injuries.
| End Use | Project Type | Project Cost | Stories | Non-building Height | Fatality | ||
|---|---|---|---|---|---|---|---|
| Powerline, transmission line | Maintenance or repair | $250,000 to $500,000 | 106 | X | |||
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation | Construction |
|---|---|---|---|---|---|---|---|
| 1 | 303119036 | Fatality | Electric Shock | Electrical power installers and repairers | Distance of Fall: feet Worker Height Above Ground/Floor: feet Cause: Temporary work (buildings, facilities) Fatality Cause: Electric shock, other and unknown cause |
||
| 2 | 303119036 | Hospitalized injury | Electric Shock | Electrical power installers and repairers | Distance of Fall: feet Worker Height Above Ground/Floor: feet Cause: Temporary work (buildings, facilities) Fatality Cause: Electric shock, other and unknown cause |