Accident Report Detail
Accident Summary Nr: 170162036 - Employee killed in flash fire at paint factory
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 112002738 | 07/15/1991 | 5231 | 0 | Frazee Paint & Wallcovering |
Abstract: On July 12, 1991, Employee #1 was working in a 4 ft 1/2 in. area between a forklift and a mill in the oil base area of Frazee Industry's main paint manufacturing facility when a flash fire occurred. Vapors and/or hazardous materials ignited, sending flames from the ground level to the 18 ft ceiling; the fire set off 23 sprinkler heads. Employee #1, who had been working an estimated 5 ft from an open drum of MEK/toluene, was killed. A propane forklift, not approved for the environment, was found with its engine running near a 60 hp mixing unit. Also in the immediate area was an unrepaired leaking toluene pipe fitting that had leaked for about two weeks prior to the fire. In addition, a 55 gallon drum and small 1 gallon open container of MEK/toluene were commonly used to clean mixer blades and tubs. A floor vapor recovery system had been installed, but its adequacy was not periodically monitored. Fire retardant clothing was not provided for the work environment, which contained a high number of flammables. Bonding and grounding procedures were not ensured. A language barrier may have been a factor in the accident.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 112002738 | Fatality | Burn/Scald(Heat) | Chemical technicians |