Accident Report Detail
Accident Summary Nr: 165649.015 - Employee dies from head trauma when shocked, fell off ladder
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1740414.015 | 04/10/2024 | 238210 | Accurate Electric Construction Inc |
Abstract: At 8:00 a.m. on April 10, 2024, an employee working as an electrician for an electrical contractor was working alone in a commercial building. The employee was using a 10-foot stepladder to access an area inside a drop ceiling to verify that the switching was correct out of an energized lighting contactor. The employee contacted an energized wire inside the circuit being checked above the ceiling. The employee was shocked causing him to fall off the stepladder approximately 10 feet to the concrete ground below. The employee died from head trauma from impact with the concrete ground.
| End Use | Project Type | Project Cost | Stories | Non-building Height | Fatality | ||
|---|---|---|---|---|---|---|---|
| Commercial building | New project or new addition | 1 | X | ||||
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation | Construction |
|---|---|---|---|---|---|---|---|
| 1 | 1740414.015 | 37 | M | Fatality | Electricians | Distance of Fall: 10 feet Worker Height Above Ground/Floor: 10 feet Cause: Interior plumbing, ducting, electrical work Fatality Cause: |