Accident Report Detail
Accident Summary Nr: 143248.015 - Employee suffers burns from energized utility line
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1565879.015 | 11/29/2021 | 562910 | Entact, Llc |
Abstract: At 7:55 a.m. on November 17, 2021, an employee was repositioning orange plastic fencing markers on the line from an aerial lift basket within one foot of an electric utility line. After engaging an air brake on the line approximately 430 feet away, a coworker verified that the brake was engaged, and a multi-hasp lock and tag were placed on the air brake control. However a voltage detector was not used to verify that the line was de-energized. As the employee threw the fencing on to the line, an arc occurred between the line and the employee. A jumper wire on the utility side of the switch had moved out of position and made direct contact with the switch, bypassing the air gap created by the ground switch. Under the bypass condition, the line had approximately 10 kV of electricity. The employee was hospitalized for treatment of burns to right hand, with hole under middle finger through palm, burns to left hand, exit hole on left forearm.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1565879.015 | 54 | M | Hospitalized injury | Laborers, except construction |
Translate